National Journeyman Electrician (NEC 2023) Practice Test
Free practice for the Journeyman Electrician Practice Exam (National, NEC 2023). Tap an answer to see if you are right, why, and which code section to look up.
Questions are checked against public sources. They are not yet reviewed by a licensed professional.
About the exam
Code edition: NEC 2023
Written exam
80
questions (80 scored)
4 h
time
70%
to pass
Open book
Topic weights are provisional until the candidate bulletin is reviewed.
Free practice questions
Question 1
According to the NEC, what is the main purpose of the Code?
Correct answer: Protecting people and property from electrical hazards
NEC 90.1
Article 90 states that the Code exists for the practical safeguarding of persons and property. It also says it is not a design specification or an instruction manual for untrained persons.
Question 2
According to the NEC, how many services may a building generally be supplied by?
Correct answer: One
NEC 230.2
Section 230.2 limits a building to one service unless one of the listed special conditions applies (fire pumps, large loads, different characteristics and similar). Exceptions are ignored here.
Question 3
According to the NEC, the conductors running from the main service panel of a house to a subpanel in a detached garage are:
Correct answer: A feeder
NEC 100
Conductors between the service equipment and the final branch-circuit overcurrent devices (here, in the garage subpanel) are a feeder.
Question 4
According to the NEC, which dwelling location requires GFCI protection for 125 V, 15 A and 20 A receptacles?
Correct answer: Bathrooms
NEC 210.8(A)
Section 210.8(A) lists bathrooms first among the dwelling locations that need GFCI protection for receptacles. Bedrooms, hallways and dining rooms are AFCI locations, not GFCI locations.
Question 5
According to the NEC, what is the general rule for the conductors of one circuit, including the grounded conductor and EGC?
Correct answer: They must be in the same raceway, cable, trench or cord
NEC 300.3(B)
Section 300.3(B) keeps all conductors of the same circuit together to limit inductive heating and keep circuit impedance low.
Question 6
According to the NEC, how must listed or labeled equipment be installed and used?
Correct answer: As the instructions in its listing or labeling require
NEC 110.3(B)
Section 110.3(B) ties the installation of listed or labeled equipment to the instructions that come with the listing or labeling.
Question 7
A 10-hp, 460-V, three-phase motor has a nameplate current of 13 A. Which current is used to size its branch-circuit conductors?
Correct answer: The full-load current from the Code's motor table
NEC 430.6(A)(1)
Section 430.6(A)(1) requires the table full-load current (not the nameplate) for sizing conductors, switches and short-circuit and ground-fault protection of general motors.
Question 8
A disconnect is required to be lockable in the open (off) position. What does the NEC require of the locking provision?
Correct answer: It stays in place with or without the lock
NEC 110.25
Section 110.25 requires the locking provision to remain in place with or without the lock installed; portable means that are removed with the lock do not qualify.
Question 9
In the hazardous location system, what separates Class I, Division 1 from Class I, Division 2?
Correct answer: In Division 1 the hazard exists in normal operation; in Division 2 only under abnormal conditions
NEC 500.5(B)
Under 500.5(B), Division 1 locations have ignitible concentrations under normal conditions; Division 2 locations have them only through abnormal events such as leaks or ventilation failure.
Question 10
In one- and two-family dwellings, what is the maximum PV system dc circuit voltage the NEC permits?
Correct answer: 600 V
NEC 690.7
Section 690.7 limits PV dc circuits to 600 V in one- and two-family dwellings and 1,000 V on or in other buildings.
Question 11
According to the NEC, which installation is outside the scope of the Code?
Correct answer: Utility-controlled generation and transmission equipment
NEC 90.2
Section 90.2 lists what is not covered, including utility-controlled installations used for generation, transmission or distribution. Conductors connecting premises to the supply are covered.
Question 12
According to the NEC, may branch-circuit conductors be installed in the same raceway as service conductors?
Correct answer: No, only service conductors may be in a service raceway
NEC 230.7
Section 230.7 keeps other conductors out of service raceways and service cables (grounding conductors and bonding jumpers are allowed). Service conductors are unprotected on the line side, so other circuits are kept apart.
Question 13
According to the NEC, unless the equipment is listed for 100% operation, feeder conductors must have an ampacity of at least the noncontinuous load plus what percentage of the continuous load?
Correct answer: 125%
NEC 215.2(A)(1)
Section 215.2(A)(1) requires the feeder ampacity to be at least the noncontinuous load plus 125% of the continuous load (before any adjustment or correction).
Question 14
According to the NEC, in a dwelling, receptacles in a garage whose floor is at grade level must have:
Correct answer: GFCI protection
NEC 210.8(A)
Section 210.8(A) requires GFCI protection for receptacles in garages and in accessory buildings with a floor at or below grade not intended as habitable rooms.
Question 15
According to the NEC, conductors of 120/240 V and 480Y/277 V systems may share a raceway when:
Correct answer: All insulation is rated for the highest voltage present
NEC 300.3(C)(1)
Section 300.3(C)(1) allows conductors of different systems of 1000 V or less in the same raceway, cable or enclosure if every conductor's insulation is rated at least the maximum voltage applied to any conductor there.
Question 16
A knockout was removed from a panelboard but no raceway or cable was installed in it. According to the NEC, what must be done with the opening?
Correct answer: Close it so it protects about as well as the enclosure wall
NEC 110.12(A)
Under 110.12(A), unused openings other than those for mounting or drainage must be closed so the protection is substantially equivalent to the wall of the equipment.
Question 17
Which current is used to size the separate overload protection of a general-purpose motor?
Correct answer: The nameplate full-load current
NEC 430.6(A)(2)
Section 430.6(A)(2) bases separate motor overload protection on the motor nameplate current rating.
Question 18
Three-way and four-way switches must be wired so that all switching is done in which conductor?
Correct answer: The ungrounded conductor only
NEC 404.2(A)
Section 404.2(A) requires three-way and four-way switches to switch only the ungrounded circuit conductor.
Question 19
A textile mill has easily ignitible fibers and flyings in the air. Which hazardous location class applies?
Correct answer: Class III
NEC 500.5(D)
Section 500.5(D) defines Class III locations by ignitible fibers or flyings; Class I is gases and vapors and Class II is combustible dust.
Question 20
Why is a PV string's maximum voltage figured at the lowest expected ambient temperature?
Correct answer: Module open-circuit voltage rises as temperature drops
NEC 690.7(A)
Section 690.7(A) corrects the rated open-circuit voltage for the lowest expected ambient temperature, because Voc increases as cell temperature falls.
Practice format: a typical journeyman written test. Local exams vary.
Open book: bring the code book your board allows; check your candidate bulletin for what may be tabbed or marked.
Questions are written to the 2023 NEC, the edition this exam tests.
Ignore code exceptions and optional methods unless a question tells you to use them.
Conductors are copper unless the question says otherwise.
For states and cities without a state journeyman license. Local exams (often ICC or NASCLA) differ; check with your city or county.
Unofficial practice; not affiliated with the licensing board or the test vendor.
Frequently asked questions
How is the Journeyman Electrician Practice Exam (National, NEC 2023) structured?
It has Written exam (80 questions, 4 h, 70%). You need to pass each part.
Is the exam open book?
Yes. You may bring the NEC 2023 code book, so this practice cites the section to look up instead of quoting it.
Can I take the exam in Spanish?
Some exams are offered in Spanish; check your candidate bulletin. Every question here is available in Spanish too.
Are these the real exam questions?
No. SkillPermit Pro is an independent study tool. Questions are written in our own words; they are not taken from the exam and are not endorsed by any licensing agency or testing vendor.
Ready for the real exam?
Get every question, unlimited calculation practice and timed mock exams in the app.
Coming soon
Download on the App Store
Coming soon
Get it on Google Play
Not affiliated with any state agency, TDLR, PSI, NFPA, EPA or CSLB. NEC® and National Electrical Code® are registered trademarks of NFPA.
Practice questions are written in our own words and cite code sections by number. Always study from your own copy of the code and the official candidate bulletin.