Special occupancies: Texas Journeyman Electrician Practice Questions
Pools, hazardous locations, RVs and mobile homes, marinas, health care, emergency systems.
Often missed
On the real exam: about 6 code questions and 3 calculations from this topic.
Question 1
Which NEC article covers swimming pools, spas and hot tubs?
Correct answer: Article 680
NEC 680
Pools, fountains, spas and hot tubs are in Article 680.
Question 2
A Class I hazardous location is one where the hazard comes from:
Correct answer: Flammable gases, vapors or liquids
NEC 500.5(B)
Class I is flammable gases or vapors; Class II is combustible dust; Class III is ignitible fibers and flyings.
Question 3
A grain elevator with combustible dust in the air is classified as a:
Correct answer: Class II location
NEC 500.5(C)
Combustible dust puts a location in Class II.
Question 4
Which NEC article covers health care facilities?
Correct answer: Article 517
NEC 517
Health care facilities are in Article 517. 511 is commercial garages, 518 is assembly occupancies and 547 is agricultural buildings.
Question 5
Legally required emergency systems (such as exit and egress lighting) are covered by:
Correct answer: Article 700
NEC 700
Emergency systems are Article 700; 701 is legally required standby, 702 is optional standby, 705 is interconnected power sources.
Question 6
Which NEC article covers marinas, boatyards and docking facilities?
Correct answer: Article 555
NEC 555
Marinas and docking facilities are in Article 555; 550 is mobile homes and 551 is recreational vehicles and RV parks.
Question 7
In the hazardous location system, what separates Class I, Division 1 from Class I, Division 2?
Correct answer: In Division 1 the hazard exists in normal operation; in Division 2 only under abnormal conditions
NEC 500.5(B)
Under 500.5(B), Division 1 locations have ignitible concentrations under normal conditions; Division 2 locations have them only through abnormal events such as leaks or ventilation failure.
Question 8
A textile mill has easily ignitible fibers and flyings in the air. Which hazardous location class applies?
Correct answer: Class III
NEC 500.5(D)
Section 500.5(D) defines Class III locations by ignitible fibers or flyings; Class I is gases and vapors and Class II is combustible dust.
Question 9
Gasoline and propane vapors belong to which Class I material group?
Correct answer: Group D
NEC 500.6(A)
Section 500.6(A) places gasoline, propane and similar materials in Group D; acetylene is Group A, hydrogen Group B, and Group E is a Class II (metal dust) group.
Question 10
Grain dust and flour dust belong to which Class II group?
Correct answer: Group G
NEC 500.6(B)
Section 500.6(B) puts grain, flour, starch, wood and plastic dusts in Group G; Group E is metal dust and Group F is carbonaceous dust such as coal.
Question 11
What does the temperature class (T-code) marked on hazardous location equipment tell you?
Correct answer: The highest surface temperature the equipment can reach
NEC 500.8(C)
Section 500.8(C) requires a temperature class marking that shows the equipment's maximum surface temperature, which must stay below the autoignition temperature of the gas or dust present.
Question 12
Which protection technique is typical for equipment in a Class II, Division 1 location?
Correct answer: Dust-ignitionproof
NEC 500.7
Section 500.7 lists dust-ignitionproof equipment for Class II, Division 1; explosionproof is the Class I, Division 1 technique and nonincendive is a Division 2 technique.
Question 13
Threaded conduit joints in a Class I, Division 1 location must be made up with at least how many fully engaged threads?
Correct answer: 5
NEC 500.8(E)(1)
Section 500.8(E)(1) requires NPT-threaded conduit and fittings to be made wrenchtight with at least five full threads fully engaged.
Question 14
According to the NEC, what is required in each conduit run that leaves a Class I, Division 1 location?
Correct answer: A conduit seal at the boundary
NEC 501.15
Section 501.15 requires a sealing fitting in each conduit run that leaves a Class I, Division 1 location, so gases and vapors cannot travel through the conduit into the unclassified area.
Question 15
In Class I, Division 1, how close to an enclosure containing arcing devices must the conduit seal be?
Correct answer: Within 18 in
NEC 501.15(A)(1)
Section 501.15(A)(1) requires seals within 18 in (450 mm) of enclosures that contain arcing or high-temperature devices.
Get every question, unlimited calculation practice and timed mock exams in the app.
Coming soon
Download on the App Store
Coming soon
Get it on Google Play
Not affiliated with any state agency, TDLR, PSI, NFPA, EPA or CSLB. NEC® and National Electrical Code® are registered trademarks of NFPA.
Practice questions are written in our own words and cite code sections by number. Always study from your own copy of the code and the official candidate bulletin.